28

2026

-

07

AC Power SPD Type 1 vs Type 2: Selection Guide for Industrial Applications

Compare AC power SPD Type 1 (10/350μs) and Type 2 (8/20μs) by test waveform, installation location, protection level Up, and application scenarios to support IEC 61643-11 compliant surge protector selection in low-voltage distribution systems.


Selecting the appropriate AC power surge protective device (SPD) is a key consideration for protecting low-voltage distribution systems in industrial environments. This guide compares Type 1 and Type 2 SPDs defined by IEC 61643-11, examining their test waveforms, installation locations, protection levels, and application scenarios to help engineers make informed selection decisions.

Why Type 1 vs Type 2 Comparison Matters

In industrial facilities, transient overvoltages from lightning strikes and switching operations can propagate through low-voltage distribution networks and affect sensitive equipment. Surge protective devices are designed to limit these transient voltages and divert surge current away from protected loads. However, not all AC SPDs are tested the same way, and selecting an inappropriate type can lead to inadequate protection or unnecessary cost.

The IEC 61643-11 standard classifies AC power SPDs into test classes, among which Type 1 and Type 2 are most commonly applied in industrial low-voltage installations. Understanding the distinction between them—particularly in terms of test waveform energy, installation placement, and protection level—is a foundation for sound surge protector selection. This article references the AC power SPD product range that Cresin manufactures in compliance with IEC 61643-11.

IEC 61643-11 Classification: Type 1 and Type 2 Defined

Under IEC 61643-11, an SPD's test class describes the standardized surge current waveform it has been evaluated against, rather than simply its rated current value. This classification guides where the device is intended to be installed within a lightning protection zone (LPZ) structure.

Type 1 SPD (Class I test) is tested with an impulse current waveform of 10/350μs, simulating the partial lightning current that may enter a building's electrical system following a direct lightning strike to an external lightning protection system. Type 1 devices are generally intended for installation at the origin of the installation—typically at the main distribution board—where they divert a portion of the lightning current to the earthing system.

Type 2 SPD (Class II test) is tested with a nominal discharge current (In) and a maximum discharge current (Imax) using an 8/20μs waveform. This waveform represents the shorter-duration surges associated with indirect lightning effects and switching transients. Type 2 SPDs are typically installed at sub-distribution boards or closer to end equipment, where residual surge energy from upstream protection is further limited.

Note: A third category, Type 3 (Class III test), is tested with a combination wave at lower energy and is intended for outlet-level protection. It may complement a Type 1/Type 2 cascade but is outside the scope of this comparison.

Test Waveforms: 10/350μs vs 8/20μs Explained

The distinction between the 10/350μs and 8/20μs test waveforms is frequently discussed in Type 1 vs Type 2 SPD comparison, because it relates to the energy the device is expected to handle.

A 10/350μs waveform rises to peak in approximately 10 microseconds and decays to half-value in around 350 microseconds. The long duration means the total charge and specific energy (action integral) transferred is substantially greater than that of a shorter waveform of the same peak amplitude. This is why Type 1 testing uses an impulse current (Iimp) characterized by charge transfer (Q) and specific energy (W/R), rather than the peak current value used in Type 2 testing.

An 8/20μs waveform reaches peak in about 8 microseconds and decays to half-value in approximately 20 microseconds. Although the peak current of a Type 2 test may be numerically similar to or higher than a Type 1 Iimp value, the total energy is considerably lower because the duration is much shorter. Engineers comparing Type 1 vs Type 2 SPD specifications should consider the underlying waveform rather than comparing peak current figures in isolation.

Comparison of the 10/350μs (Type 1) and 8/20μs (Type 2) test current waveforms specified in IEC 61643-11. T1 = front time to peak, T2 = time to half value.
Comparison of the 10/350μs (Type 1) and 8/20μs (Type 2) test current waveforms specified in IEC 61643-11. T1 = front time to peak, T2 = time to half value.

This energy difference has implications for component selection. A Type 1 SPD typically employs components capable of absorbing higher energy—such as spark gaps or high-energy MOV combinations—while a Type 2 SPD generally relies on metal oxide varistors (MOVs) optimized for a more compact footprint suitable for sub-distribution panels.

Installation Locations in Low-Voltage Distribution Systems

Where a Type 1 or Type 2 SPD is installed is closely related to its test class. The Lightning Protection Zone (LPZ) concept, defined in IEC 62305, provides a framework for placing SPDs at zone boundaries to progressively reduce surge threat levels closer to sensitive equipment.

A Type 1 SPD is typically installed at the boundary between the external environment (LPZ 0) and the internal installation (LPZ 1)—that is, at the main distribution board or incoming supply point. This is where partial lightning current may enter the system, and the SPD diverts the majority of this energy to the earthing system.

A Type 2 SPD is usually installed at the boundary between LPZ 1 and LPZ 2, such as at sub-distribution boards feeding load circuits. At this stage, the surge has been partially attenuated by upstream protection, and the Type 2 device further limits the residual voltage. In many industrial installations, a combined approach—Type 1 at the origin followed by Type 2 at sub-distribution—provides a coordinated multi-stage scheme.

Typical installation locations of Type 1 SPD at the main distribution board and Type 2 SPD at sub-distribution boards, mapped to IEC 62305 lightning protection zones.
Typical installation locations of Type 1 SPD at the main distribution board and Type 2 SPD at sub-distribution boards, mapped to IEC 62305 lightning protection zones.

An SPD's effectiveness also depends on connecting conductor length and coordination with adjacent devices. Excessive lead length can introduce additional voltage drop during a surge event, reducing the protection level delivered to the load—a consideration applicable to both Type 1 and Type 2 installations.

Protection Level (Up): What It Means and How to Compare

The protection level, designated Up, represents the residual voltage across the SPD terminals when the device conducts a nominal discharge current. A lower Up generally indicates less voltage is let through to the protected equipment. For effective protection, the Up should be below the rated impulse withstand voltage (Uw) of the equipment, with a suitable safety margin.

Type 1 SPDs, because they handle higher-energy 10/350μs impulses, may exhibit a relatively higher Up at rated impulse current compared with a Type 2 device tested at 8/20μs. This is one reason a Type 1 device alone may not provide sufficient protection for sensitive equipment, and why a downstream Type 2 SPD is often applied to achieve a lower residual voltage. When comparing datasheets, the Up value should be reviewed together with the corresponding test current and waveform.

Another parameter worth examining is the maximum continuous operating voltage (Uc), the steady-state voltage the SPD can withstand without conducting. Selecting a Uc appropriate for the system's nominal voltage helps ensure long-term reliability. For example, in a 230/400 V TN-S system, a Uc of 385 V or higher is commonly selected for Type 2 AC SPDs such as the CSMS-B40 series, rated for AC 385 V / 420 V / 440 V systems.

Cresin CSMS-B40 series AC power SPD, a Type 2 / Class II device rated for Imax 40 kA at Uc 385 V, suitable for industrial sub-distribution boards.
Cresin CSMS-B40 series AC power SPD, a Type 2 / Class II device rated for Imax 40 kA at Uc 385 V, suitable for industrial sub-distribution boards.

Type 1 vs Type 2 SPD Parameter Comparison Table

The table below summarizes the principal differences between Type 1 and Type 2 AC power SPDs as defined by IEC 61643-11, providing a reference for surge protector selection.

ParameterType 1 (Class I)Type 2 (Class II)
Test standardIEC 61643-11 Class I testIEC 61643-11 Class II test
Test waveform10/350μs impulse current8/20μs nominal discharge current
Current rating basisIimp (impulse current), defined by peak, charge Q, specific energy W/RIn (nominal) and Imax (maximum discharge current)
Typical Iimp values12.5 kA, 15 kA, 25 kA (per pole)Not applicable to Type 2 classification
Typical In / Imax valuesMay also carry Type 2 ratings (combination Type 1+2)In 20 kA, Imax 40 kA (e.g., CSMS-B40)
Primary installation locationMain distribution board / origin (LPZ 0 → 1)Sub-distribution board / near loads (LPZ 1 → 2)
Surge source addressedDirect lightning current entering the systemIndirect lightning and switching transients
Protection level UpGenerally higher at rated IimpGenerally lower, suitable for equipment protection
Internal component emphasisSpark gaps or high-energy MOV combinationsMOVs optimized for compact sub-distribution use
Typical use caseBuildings with external lightning protection; high exposure sitesMost industrial and commercial sub-distribution panels

Cascaded Protection: Coordinating Type 1 and Type 2

In many industrial installations, a single SPD stage does not address all threat levels effectively. A cascaded approach—Type 1 at the main distribution board and one or more Type 2 SPDs at sub-distribution boards—allows each stage to handle surge energy appropriate to its location, while progressively reducing the residual voltage delivered to end equipment.

For this cascade to function as intended, coordination between stages is important. If upstream and downstream SPDs are not coordinated, the downstream device may conduct more current than expected, potentially leading to premature wear. Coordination depends on the Up and Uc of each device, the cable length between stages, and the surge characteristics. Decoupling elements or sufficient cable length (commonly on the order of 10 metres, depending on device types) are often applied to support proper energy sharing between stages.

Cascaded coordination between Type 1 and Type 2 AC SPDs progressively reduces residual surge voltage (Up) delivered to protected equipment.
Cascaded coordination between Type 1 and Type 2 AC SPDs progressively reduces residual surge voltage (Up) delivered to protected equipment.

When both protection stages are required, devices classified as combined Type 1+2 (tested to both Class I and Class II requirements) are available and can simplify specification. These devices carry both an Iimp rating and an In/Imax rating, allowing them to serve either as the origin-of-installation protector or as a high-capacity sub-distribution stage depending on the system design.

Application Scenarios: When to Choose Which

The choice between Type 1, Type 2, or a combination depends on the specific characteristics of the installation. Several common industrial scenarios illustrate how the selection decision is approached:

Scenario A — Facility with external lightning protection system. When a building is equipped with an external LPS in a region with notable lightning activity, a Type 1 SPD at the main distribution board is generally recommended to manage partial lightning current entering via the service entrance. A downstream Type 2 stage at sub-distribution boards further protects sensitive loads.

Scenario B — Industrial plant without external LPS. Where the primary surge sources are indirect lightning and switching transients, Type 2 SPDs at sub-distribution boards often form the core of the protection scheme. Whether the incoming supply also requires a Type 1 stage depends on a risk assessment per IEC 62305.

Scenario C — Sensitive equipment room. For installations housing equipment with low impulse withstand voltage, such as servers or precision controllers, a multi-stage cascade (Type 1 at origin, Type 2 at sub-distribution, and in some cases Type 3 near the equipment) is typically applied to achieve a low Up at the equipment terminals.

For projects requiring a combined assessment of SPD type, Uc, Up, and pole configuration for a given earthing arrangement, the Cresin technical team provides selection support. Readers are welcome to contact us for guidance tailored to a specific installation, or refer to the power distribution surge protection solutions for reference configurations.

Selection Considerations to Review

When evaluating Type 1 vs Type 2 SPD options, several considerations are worth reviewing:

  • Comparing peak current without considering waveform. An Imax of 40 kA (8/20μs) and an Iimp of 25 kA (10/350μs) are not directly equivalent; the energy content differs considerably. Selection should reference the relevant test class rather than peak current alone.
  • Overlooking Up vs. equipment Uw. The Up should be evaluated at the current level relevant to the installation's exposure and coordinated with the equipment's impulse withstand voltage.
  • Lead length and wiring practices. Excessive connecting lead length can add inductive voltage drop during a surge, raising the effective protection level at the load terminals.
  • Backup protection coordination. SPDs require suitable upstream overcurrent protection (a dedicated backup disconnector or appropriately selected fuse/breaker) to disconnect the device safely at end of life. Reference the IEEE surge protection guidelines and the relevant sections of IEC 61643-11.

Frequently Asked Questions

Q1: What is the main difference between Type 1 and Type 2 AC SPDs?

The primary difference lies in the test waveform and corresponding energy level. Type 1 SPDs are tested with a 10/350μs impulse current (Class I per IEC 61643-11), simulating partial lightning current from a direct strike, while Type 2 SPDs are tested with an 8/20μs waveform (Class II) representing indirect lightning and switching surges.

Q2: Can a Type 2 SPD replace a Type 1 SPD?

Generally, a Type 2 SPD is not intended as a direct replacement for a Type 1 SPD at the origin of an installation where partial lightning current may enter. Type 1 devices are tested for the higher energy of the 10/350μs waveform. In many installations, Type 1 and Type 2 serve as complementary stages. A combined Type 1+2 device may be used where both functions are required at one location.

Q3: Where should a Type 1 SPD be installed?

A Type 1 SPD is typically installed at the main distribution board—at the boundary between LPZ 0 and LPZ 1—where the service entrance may be exposed to partial lightning current, particularly in buildings with an external lightning protection system. The specific point should be confirmed based on the site's single-line diagram and a risk assessment.

Q4: How do I choose the Up value for an AC SPD?

The protection level Up should be below the rated impulse withstand voltage (Uw) of the equipment being protected, with a suitable safety margin. A lower Up generally provides better protection for sensitive equipment. When reviewing a datasheet, confirm the test current at which Up is specified, as the value can vary with the discharge current magnitude.

Q5: Is a Type 1 SPD required without an external lightning protection system?

The requirement depends on a risk assessment (commonly referenced to IEC 62305) that considers local lightning density, building height, and the consequences of equipment failure. In some installations without an external LPS, a Type 1 stage may still be recommended; in others, Type 2 protection at sub-distribution may be considered sufficient.

Q6: How are Type 1 and Type 2 SPDs coordinated in a cascaded system?

Coordination involves ensuring the upstream device handles the higher-energy portion of the surge while the downstream device further limits residual voltage, without the downstream device being exposed to more current than its rating allows. Factors include the Up and Uc of each device, the cable length between stages, and the use of decoupling elements where required.

Summary

Type 1 and Type 2 AC power SPDs serve complementary roles in industrial low-voltage distribution systems. Type 1 devices, tested with the 10/350μs impulse current defined in IEC 61643-11, are intended for the origin of an installation where partial lightning current may enter, while Type 2 devices, tested with the 8/20μs waveform, are applied at sub-distribution boards to limit residual voltage reaching equipment. The choice between them—and whether a cascaded arrangement is appropriate—depends on the installation's lightning exposure, the presence of an external lightning protection system, the impulse withstand voltage of protected equipment, and a site-specific risk assessment.

By evaluating test waveform, installation location, protection level Up, and application scenario together—rather than relying on any single parameter—engineers can approach AC SPD selection in a manner consistent with IEC 61643-11 and suited to the protection requirements of their installation.


Shandong Cresin Electric Co., Ltd.      Privacy Policy

Follow Us

Contact Us

Address: No. 978 Tianchen Road, High-tech Zone, Jinan, Shandong,China

CAN’T FIND THE PRODUCT?

The product range includes production technologies for smart capacitors, digital display meters, surge protectors, dedicated backup protection devices for surge protectors, self-resetting over/under-voltage protectors, control and protection switches, and automatic transfer switches for dual power supplies.

Search HistoryClear All Records
Up to 8 search history entries will be displayed.~
全部
  • 全部
  • 产品管理
  • 新闻资讯
  • 介绍内容
  • 企业网点
  • 常见问题
  • 企业视频

LEAVE US A MESSAGE