CSMS-B40
Un(V):
DC12/24/48/120/220/380/750/1000
Uc(V):
DC15/30/60/175/275/505/1060/1200
In (8/20 μs):
20kA
Imax(8/20 μs):
40kA
Mode of Protection:
L/N-PE; L-N, N-PEReference Standards:
IEC 61643-11OEM/ODM Acceptable
Additional Function:
Thermal Tripping Protection, Status Indicator, and Remote SignalingTechnical Parameters
|
SPD Model |
CSMS-B40 |
|||||||
|
Nominal voltage Un (V) |
DC12 |
DC24 |
DC48 |
DC120 |
DC220 |
DC380 |
DC750 |
DC1000 |
|
Maximum continuous operating voltage Uc (V) |
DC15 |
DC30 |
DC60 |
DC175 |
DC275 |
DC505 |
DC1060 |
DC1200 |
|
Nominal discharge current In(8/20µs) |
20kA |
20kA |
20kA |
20kA |
20kA |
20kA |
20kA |
20kA |
|
Maximum discharge current Imax(8/20µs) |
40kA |
40kA |
40kA |
40kA |
40kA |
40kA |
40kA |
40kA |
|
Voltage protection level Up |
≤0.5kV |
≤0.5kV |
≤0.5kV |
≤0.85kV |
≤1.5kV |
≤1.5kV |
≤3.3kV |
≤4.0kV |
|
Response time |
≤25ns |
≤25ns |
≤25ns |
≤25ns |
≤25ns |
≤25ns |
≤25ns |
≤25ns |
|
Leakage current |
≤15μA |
≤15μA |
≤15μA |
≤15μA |
≤15μA |
≤15μA |
≤15μA |
≤15μA |
|
Sectional area of Wire |
6-35mm² |
|||||||
|
Maximum backup fuse |
125A gl/gG |
|||||||
|
Connection type |
Terminal wiring (torque: 2.5Nm) |
|||||||
|
Remote signal contact point |
Optional(Alarm contact strength AC:250V/0.5A,125V/2A; DC:30V/2A)(torque:0.25Nm)(Sectional area of Wire:0.5-1.5mm²) |
|||||||
|
485 Communication |
Optional |
|||||||
|
Dimensions |
18mm/P |
|||||||
|
Number of Poles |
2P |
3P |
||||||
|
Reference Standards |
IEC61643-11;GB/T18802.11 |
|||||||
|
Case material |
Flame retardant plastic |
|||||||
|
Mounting |
DIN rail 35 mm |
|||||||
|
Ambient air temperature for operation |
-40℃~+80℃ |
|||||||
|
Ambient air temperature for storage |
||||||||
|
Relative humidity |
5~95%(No condensation) |
|||||||
|
Degree of protection of enclosure (IP code) |
IP20 |
|||||||
|
Operating altitude |
≤3000m |
|||||||
|
Atmosphere pressure |
70kPa~106kPa |
|||||||
|
Warranty period |
3 years |
|||||||
SPD Schematic
|
2P SPD Schematic |
3P SPD Schematic |
Wiring Diagram
|
2P SPD Wiring Diagram |
3P SPD Wiring Diagram |
Dimensions (mm)
|
CSMS-B40 Dimension figure |
RELATED PRODUCTS
PV DC SPD->DC Power SPD
Un(V) :
DC600V/1000V/1200V/1500V
Uc(V) :
DC670V/1200V/1500V/1800V
In (8/20 μs):
20kA
Imax(8/20 μs):
40kA
Reference Standards:
IEC 61643-31OEM/ODM Acceptable
Additional Function:
Thermal Tripping Protection, Status Indicator, and Remote SignalingShandong Cresin Electric Co., Ltd. Privacy Policy
Contact Us
Address: No. 978 Tianchen Road, High-tech Zone, Jinan, Shandong,China
CAN’T FIND THE PRODUCT?
The product range includes production technologies for smart capacitors, digital display meters, surge protectors, dedicated backup protection devices for surge protectors, self-resetting over/under-voltage protectors, control and protection switches, and automatic transfer switches for dual power supplies.